Cylinders placement

5 pts.
Tags:
FM200
FSS
novec
Why the cylinders of fm200 and novec are installed inside rooms? Like why they are installed inside datacenter rooms or server rooms?
1

Answer Wiki

Thanks. We'll let you know when a new response is added.

This site is geared more towards computers, programming and such. I did some info on your question but it may vary based on state codes. 

FM-200 cylinders may be placed in or out of the protected space, depending on the needs of the client. Both NFPA 2001, Clean Agent Standard and ISO 14520 allow the cylinders to be placed within or outside the protected space. It is always a good idea to keep the cylinders as close to the protected area as possible and remember to account for ease of access for service and maintenance

Discuss This Question: 1  Reply

 
There was an error processing your information. Please try again later.
Thanks. We'll let you know when a new response is added.
Send me notifications when members answer or reply to this question.
  • ToddN2000
    Another possible reason it for security against tampering. Most data centers I have worked with are secure. A key card or combination is needed to gain entry. Placing the canisters with in the data center means only those with access can get close to them. They can still be secured within another room in the data center itself.

    129,715 pointsBadges:
    report

Forgot Password

No problem! Submit your e-mail address below. We'll send you an e-mail containing your password.

Your password has been sent to:

To follow this tag...

There was an error processing your information. Please try again later.

Thanks! We'll email you when relevant content is added and updated.

Following

Share this item with your network: