Can dust trigger the discharge of a functional FM-200 fire suppression system?

5 pts.
Tags:
Fire suppression
Can dust trigger the discharge of a functional fm-200 fire suppression system?

Answer Wiki

Thanks. We'll let you know when a new response is added.
The simple answer is YES.  We just had a complete data center outage due to someone using a shop vacuum within the data center without first placing our FM-200 into bypass mode.  As soon as 2 detectors detected the dust, the system was activated.  Unfortunately, the first action our system takes is to EPO the room which caused all power to be shut down resulting in a complete data center outage. 

Discuss This Question: 1  Reply

 
There was an error processing your information. Please try again later.
Thanks. We'll let you know when a new response is added.
Send me notifications when members answer or reply to this question.
  • stevern89
    dont know.
    you found any answer?
    25 pointsBadges: